SERVICE
REQUIREMENTS
Effective
May 1, 2000
I.
Residential Services (Overhead)
II. Residential Services (Underground)
III. Mobile and Manufactured Homes
(Overhead)
IV. Mobile and Manufactured Homes
(Underground)
V. Temporary Service Poles (Overhead)
VI. Temporary Service Poles (Underground)
VIII. Residential Primary Line Extensions
VIIII. Commercial Services
XI. Procedures for Obtaining Electric
Service
General: All wiring and electrical installations shall comply with the
current editions of the National Electric Code and the State of Tennessee’s
“Rules of Department of Commerce and Insurance, Division of Fire Prevention,
Chapter 0780-2-1, Electrical Installations”.
They shall also comply with the following special
provisions.
I. Residential Services (Overhead)
A.
Overhead Service Entrance
Conductors (weatherhead to line side of meter socket) and Service Conductors
(load side of meter socket to line side of breaker panel):
1. 60 Amp. Main – No. 6 stranded copper with THW or THWN black insulation on hot conductors. No. 6 stranded copper with THW or THWN white insulation on neutral conductor. The contractor or customer shall install these conductors from the load side of the meter socket to the line side of the main switch panel and from the line side of the meter socket to the weatherhead.
2. 100 Amp. Main – No. 2 stranded copper with THW or THWN black insulation on hot conductors, No. 4 stranded copper with THW or THWN white insulation on neutral conductor. The contractor or customer shall install these conductors from the load side of the meter socket to the line side of the main switch panel and from the line side of the meter socket to the weatherhead.
3. 200 Amp. Main – No. 3/0 stranded copper with THW or THWN black insulation on hot conductors, minimum No. 1/0 stranded copper with THW or THWN white insulation on the neutral conductor. The contractor or customer shall install these conductors from the load side of the meter socket to the line side of the main switch panel and from the line side of the meter socket to the weatherhead.
4. 225 Amp. Main – No. 4/0 stranded copper with THW or THWN black insulation on hot conductors, minimum No. 2/0 stranded copper with THW or THWN white insulation on the neutral conductor. The contractor or customer shall install these conductors from the load side of the meter socket to the line side of the main switch panel and from the line side of the meter socket to the weatherhead.
5. 400 Amp. Main – No. 500 stranded copper with THW or THWN black insulation on hot conductors, minimum No. 350 stranded copper with THW or THWN white insulation on the neutral conductor. The contractor or customer shall install these conductors from the load side of the meter socket to the line side of the main switch panel and from the line side of the meter socket to the weatherhead.
B. Overhead Service Entrance
Installations:
1.
The
customer shall provide pipe mast services at all locations where proper
clearance from ground (minimum 12’ to lowest point) cannot be obtained with
service attachment on the building. A minimum of 2” galvanized rigid steel
conduit riser is required. The conduit
riser shall be equipped with an approved roof flange and shall be securely
anchored. The conduit riser shall
extend a minimum of 36” above the roofline and a maximum rise of 42” above the
roofline. No conduit riser shall have
any splices in them, however, if a single 10’ length of rigid conduit does not
provide ample clearance, splices may be made only below the lowest of the
support brackets.
2.
The
customer shall install an approved meter socket supplied by the Tullahoma
Utilities Board (TUB) at a location on the building as designated by a TUB
Electric System representative. The
center line of the meter socket is to be installed 5 ½’ above finished grade.
C.
Other Residential Overhead
Services:
1.
These
service entrances may be installed, if proper ground clearance can be obtained,
by attachment to the building (minimum 12’ to lowest point) in galvanized thin
wall conduit. The conduit shall have
approved seal-tight couplings at the meter socket hub, and at any splices made
in the conduit run. Only two conduit
sizes are approved for this purpose: 1 ¼” I.D. for 60 amp. and 100 amp.
services; 2” I.D. for 200 amp. services.
D.
Grounding of Overhead
Residential Services:
1.
All
services 200 amp. and below shall have a minimum of No. 4 solid bare copper
conductor for grounding purposes. For services larger than 200 amp., the copper
grounding conductor used shall be as designated in the National Electric Code
Article 250-66. The conductor shall be installed and bonded to two driven
grounding electrodes spaced a minimum of 8’ apart in accordance with National
Electric Code Article 250 Part C and Part E.
II Residential Services (Underground)
A. Service Conductors (Load Side Of Meter Base To Line Side Of Switch Panel):
1. 60 Amp. Main – No. 6 stranded copper with THW or THWN black insulation on hot conductors. No. 6 stranded copper with THW or THWN white insulation on neutral conductor. The contractor or customer shall install these conductors from the load side of the meter socket to the line side of the main switch panel.
2. 100 Amp. Main – No. 2 stranded copper with THW or THWN black insulation on hot conductors, No. 4 stranded copper with THW or THWN white insulation on neutral conductor. The contractor or customer shall install these conductors from the load side of meter socket to the line side of the main switch panel.
3. 200 Amp. Main – No. 3/0 stranded copper with THW or THWN black insulation on hot conductors, minimum No. 1/0 stranded copper with THW or THWN white insulation on the neutral conductor. The contractor or customer shall install these conductors from the load side of meter socket to the line side of the main switch panel.
4. 225 Amp. Main – No. 4/0 stranded copper with THW or THWN black insulation on hot conductors, minimum No. 2/0 stranded copper with THW or THWN white insulation on the neutral conductor. The contractor or customer shall install these conductors from the load side of meter socket to the line side of the main switch panel.
5. 400 Amp. Main – No. 500 stranded copper with THW or THWN black insulation on hot conductors, minimum No. 350 stranded copper with THW or THWN white insulation on the neutral conductor. The contractor or customer shall install these conductors from the load side of meter socket to the line side of the main switch panel.
B.
Grounding of Underground (UG) Residential Services:
1.
All
services 200 amp. and below shall have a minimum of No. 4 solid bare copper
conductor for grounding purposes. For services larger than 200 amp., the copper
grounding conductor used shall be as designated in the National Electric Code
Article 250-66. The conductor shall be installed and bonded to two driven
grounding electrodes spaced a minimum of 8’ apart in accordance with National
Electric Code Article 250 Part C and Part E.
C.
Underground Service
Installations
1. Customer requirements:
a. The customer shall furnish a trench which is a minimum of 4” wide and 30” deep for the entire service run from the metering point to the pad mount transformer or service pole via a route designated by a representative of the TUB Electric System.
b. The customer shall install an approved meter socket (supplied by TUB) at a location on the building as designated by the TUB Electric System representative. The center line of the installed meter socket shall be 5 ½’ above the finished grade.
c. The customer shall install Schedule 40 polyvinyl chloride (PVC) conduit in the trench. At the pole or pad-mounted transformer, he shall install a 90-degree elbow and stub up a PVC conduit. At the meter he shall install a 90-degree elbow and shall install rigid steel conduit to the meter socket. The conduit shall be attached to the meter socket with two steel locknuts and one approved conduit bushing. The conduit sizes are as follows:
200 amp. service and below – 2 ½” conduit
201 to 400 amp. service – 3” conduit
401 to 600 amp. service – 4” conduit
larger than 600 amp. services – to be determined on site by a TUB representative.
d. The customer shall install a ¼” polypropylene rope in the conduit for cable pulling purposes.
e. The customer shall inform the TUB when trench, conduit, and meter socket are ready for inspection by the TUB Electric System representative. The customer or their representative shall be at the site during the inspection. Upon approval by the TUB, the customer shall backfill the trench or a portion of trench as designated by the TUB representative.
2. Tullahoma Utilities Board Work Performance:
a. The TUB will install and connect all cable from point of origin to the line side of the meter socket when all services charges have been paid, the State of Tennessee electrical inspections have been made and passed, and an approval certificate from the City of Tullahoma Codes Department has been issued.
b. The TUB will furnish the appropriate size and class meter socket for each meter location. No meter sockets from outside the TUB Electric System will be permitted.
c. The TUB will furnish, locate, install, and maintain the appropriate size transformer for adequate service. The TUB shall also have access at all times to the transformer locations.
3. Residential Underground Service (UG) Charges:
a. All underground service charges are borne by the customer.
b. Charges include installation by the TUB personnel as outlined in item II, C, 2 (a)(b).
c. Upon request, the customer will be provided current underground service charge information in accordance with the TUB policy E-006 “Underground Service Availability and Charges”, at the time the service is located by the TUB representative. The customer will be invoiced for UG service charges by the TUB at a later date.
d. All underground services charges must be paid at the TUB office prior to service installation.
III.
Mobile and
Manufactured Homes (Overhead)
A.
Overhead Service Entrance Conductors (weatherhead to line side of meter
socket) and Service Conductors (load side of meter socket to line side of
disconnecting means):
1. 100 Amp. Main – No. 2 stranded copper with THW or THWN black insulation on hot conductors, No. 4 stranded copper with THW or THWN white insulation on neutral conductor. The contractor or customer shall install these conductors from the load side of the meter socket to the line side of the disconnecting means and from the line side of the meter socket to the weatherhead.
2. 200 Amp. Main – No. 3/0 stranded copper with THW or THWN black insulation on hot conductors, minimum No. 1/0 stranded copper with THW or THWN white insulation on the neutral conductor. The contractor or customer shall install these conductors from the load side of the meter socket to the line side of the disconnecting means and from the line side of the meter socket to the weatherhead.
B. Overhead Service Entrance
Pole Installations:
1.
The
customer shall install at the minimum a 6” diameter treated service pole. To maintain proper clearances the pole
height and location is to be determined on site by a TUB Electric System
representative. The pole is to be
installed a minimum of 5’ below finished grade.
2.
The
customer shall install galvanized thin wall conduit or a rigid steel conduit
riser and weatherhead to 6” below the top of the pole.
3.
The
customer shall install a 5/8” eyebolt 6” below the top of the weatherhead.
4.
The
customer shall install a minimum of ¼” steel guy wire and a minimum of 5/8” x
5’ anchor rod and expanding anchor plate.
Screw type anchors will not be permitted.
5.
The
customer shall install an approved meter socket (supplied by the TUB). The center line of the installed meter
socket shall be 5 ½’ above finished grade.
C. Grounding of Mobile and
Manufactured Home Overhead Services:
1.
All
services 200 amp. and below shall have a minimum of No. 4 solid bare copper
conductor for grounding purposes. For services larger than 200 amp., the copper
grounding conductor used shall be as designated in the National Electric Code
Article 250-66. The conductor shall be installed and bonded to two driven
grounding electrodes spaced a minimum of 8’ apart in accordance with National
Electric Code Article 250 Part C and Part E.
IV.
Mobile and
Manufactured Homes (Underground)
A. Service Conductors (Load Side Of Meter Base To Line Side Of Disconnect Switch):
1. 100 Amp. Main – No. 2 stranded copper with THW or THWN black insulation on hot conductors, No. 4 stranded copper with THW or THWN white insulation on neutral conductor. The contractor or customer shall install these conductors from the load side of the meter socket to the line side of the disconnect switch.
2. 200 Amp. Main – No. 3/0 stranded copper with THW or THWN black insulation on hot conductors, minimum No. 1/0 stranded copper with THW or THWN white insulation on the neutral conductor. The contractor or customer shall install these conductors from the load side of the meter socket to the line side of the disconnect switch.
B. Underground Service Entrance Pole Installations:
1.
The
customer shall install at the minimum a 6” diameter treated service pole or 6”
x 6” treated post. The pole is to be
installed a minimum of 5’ below finished grade. The pole location is to be determined on site by the TUB Electric
System representative.
2.
The
customer shall install an approved meter socket (supplied by the TUB).
The center line of the installed meter socket shall be 5 ½’ above
finished grade.
C. Grounding of Underground
(UG) Residential Services:
1.
All
services 200 amp. and below shall have a minimum of No. 4 solid bare copper
conductor for grounding purposes. For services larger than 200 amp., the copper
grounding conductor used shall be as designated in the National Electric Code
Article 250-66. The conductor shall be installed and bonded to two driven grounding
electrodes spaced a minimum of 8’ apart in accordance with National Electric
Code Article 250 Part C and Part E.
D.
Underground Service Installations
1. Customer requirements:
a. The customer shall furnish a trench which is a minimum of 4” wide and 30” deep for the entire service run from the metering point to the pad mount transformer or service pole via a route designated by a representative of the TUB Electric System.
b. The customer shall install an approved meter socket (supplied by TUB) on service pole at location to be determined by the TUB Electric System representative. The center line of the installed meter socket shall be 5 ½’ above finished grade. The customer shall attach rigid steel conduit to the meter socket with two steel locknuts and one approved conduit bushing. The conduit shall be secured to the service pole with a minimum of two, one-hole rigid conduit straps.
c. The customer shall install Schedule 40 polyvinyl chloride (PVC) conduit in the trench. At the pole or pad-mounted transformer, he shall install a 90-degree elbow and stub up a PVC conduit. At the meter he shall install a 90-degree elbow and shall install rigid steel conduit to the meter socket. The conduit shall be attached to the meter socket with two steel locknuts and one approved conduit bushing. The conduit sizes are as follows:
200 amp. service and below – 2 ½” conduit
larger than 200 amp. service – to be determined on site by TUB representative.
d. The customer shall install a ¼” polypropylene rope in the conduit for cable pulling purposes.
e. The customer shall inform the TUB when the trench, conduit, pole, and meter socket are ready for inspection by the TUB Electric System representative. The customer or their representative shall be at the site during the inspection. Upon approval by the TUB, the customer shall backfill the trench or a portion of the trench as designated by the TUB representative.
2. Tullahoma Utilities Board Work Performance:
a. The TUB will install and connect all cable from point of origin to line side of the meter socket when all services charges have been paid, the State of Tennessee electrical inspections have been made and passed, and the approval certificate from the City of Tullahoma Codes Department has been issued.
b. The TUB will furnish the appropriate size and class meter socket for each meter location. No meter sockets from outside the TUB Electric System will be permitted.
c. The TUB will furnish, locate, install, and maintain the appropriate size transformer for adequate service. The TUB shall also have access at all times to the transformer locations.
3. Residential Underground Service Charges:
a. All underground service charges shall be borne by the customer.
b. Charges include installation by TUB personnel as outlined in item II, C, 2 (a)(b).
c. Upon request, the customer will be provided current underground service charges information in accordance with the TUB policy E-006 “Underground Service Availability and Charges” at the time the service is located by the TUB representative. The customer will be invoiced for UG service charges by the TUB at a later date.
d. All underground services charges must be paid at the TUB office prior to service installation.
V.
Temporary Service
Poles (Overhead)
A.
Overhead Service Entrance Conductors (weatherhead to line side of meter
socket) and Service Conductors (load side of meter socket to line side of
disconnect):
1. 60 Amp. Main – No. 6 stranded copper with THW or THWN black insulation on hot conductors. No. 6 stranded copper with THW or THWN white insulation on neutral conductor. The contractor or customer shall install these conductors from the load side of the meter socket to the line side of the disconnecting means and from the line side of the meter socket to the weatherhead.
2. 100 Amp. Main – No. 2 stranded copper with THW or THWN black insulation on hot conductors, No. 4 stranded copper with THW or THWN white insulation on neutral conductor. The contractor or customer shall install these conductors from the load side of the meter socket to the line side of the disconnecting means and from the line side of the meter socket to the weatherhead.
3. 200 Amp. Main – No. 3/0 stranded copper with THW or THWN black insulation on hot conductors, minimum No. 1/0 stranded copper with THW or THWN white insulation on the neutral conductor. The contractor or customer shall install these conductors from the load side of the meter socket to the line side of the disconnecting means and from the line side of the meter socket to the weatherhead.
B. Overhead Temporary Service
Entrance Pole Installations:
1.
The
customer shall install a minimum of a 4” square or a 4” diameter treated
service pole. To maintain proper
clearances, the pole height and location is to be determined on site by the TUB
Electric System representative. The
pole is to be installed a minimum of 3’ below finished grade.
2.
The
customer shall install a galvanized thin wall conduit or a rigid steel conduit
riser, and weatherhead to 6” below the top of pole.
3.
The
customer shall install a 5/8” eyebolt 6” below the top of the weatherhead.
4.
The
customer shall install bracing to support pole against tension of the TUB
service wire.
5.
The
customer shall furnish and install an approved meter socket. The center line of the installed meter
socket shall be 5 ½’ above the finished grade.
C. Grounding of Overhead
Temporary Services:
1. All
services 200 amp. and below shall have a minimum of No. 4 solid bare copper
conductor for grounding purposes. For services larger than 200 amp., the copper
grounding conductor used shall be as designated in the National Electric Code
Article 250-66. The conductor shall be installed and bonded to one driven
grounding electrode in accordance with National Electric Code Article 250 Part
C and Part E.
VI.
Temporary Service
Poles (Underground)
A.
Service Conductors (Load Side Of Meter Base To Line Side Of
Disconnect):
1. 60 Amp. Main – No. 6 stranded copper with THW or THWN black insulation on hot conductors. No. 6 stranded copper with THW or THWN white insulation on neutral conductor. The contractor or customer shall install these conductors from the load side of the meter socket to the line side of the disconnect switch.
2. 100 Amp. Main – No. 2 stranded copper with THW or THWN black insulation on hot conductors, No. 4 stranded copper with THW or THWN white insulation on neutral conductor. The contractor or customer shall install these conductors from the load side of the meter socket to the line side of the disconnect switch.
3. 200 Amp. Main – No. 3/0 stranded copper with THW or THWN black insulation on hot conductors, minimum No. 1/0 stranded copper with THW or THWN white insulation on the neutral conductor. The contractor or customer shall install these conductors from the load side of the meter socket to the line side of the disconnect switch.
B. Underground Temporary Service Entrance Pole Installations:
1.
The
customer shall install a minimum of a 4” square or a 4” diameter treated
service pole. The pole is to be installed
a minimum of 3’ below finished grade.
The pole location is to be determined on site by the TUB Electric System
representative.
2.
The
customer shall furnish and install an approved meter socket. The center line of the installed meter
socket shall be 5 ½’ above the finished grade.
NOTE: The customer may use an overhead temporary service pole as specified in Article V at underground service locations if the customer installs rigid metal conduit on the pole from 12” below grade to the weatherhead and secures conduit with rigid metal conduit straps.
C. Grounding of Underground
Temporary Services:
2. All
services 200 amp. and below shall have a minimum of No. 4 solid bare copper
conductor for grounding purposes. For services larger than 200 amp., the copper
grounding conductor used shall be as designated in the National Electric Code
Article 250-66. The conductor shall be installed and bonded to one driven
grounding electrode in accordance with National Electric Code Article 250 Part
C and Part E.
D.
Underground Temporary Service Installations
1. Customer requirements:
a. The customer shall furnish a trench which is a minimum of 4” wide and 24” deep for the entire service run from the metering point to the pad mount transformer or service pole via a route designated by a representative of the TUB Electric System.
b. The customer shall furnish and install an approved meter socket on the service pole at a location to be determined by the TUB Electric System representative. The center line of the installed meter socket shall be 5 ½’ above the finished grade. The customer shall attach rigid steel conduit to meter socket with two steel locknuts and one approved conduit bushing. Conduit shall be secured to service pole with minimum of two, one-hole rigid conduit straps. The conduit sizes are as follows:
100 amp. service and below – 1 ½” conduit
200 amp. service – 2 ½” conduit
1. Tullahoma Utilities Board Work Performance:
a. The TUB will install and connect all cable from the point of origin to the line side of the meter socket when all service charges have been paid and the State of Tennessee electrical inspections have been made and passed.
b. The TUB will furnish, locate, install, and maintain the appropriate size transformer for adequate service. The TUB shall also have access at all times to the transformer locations.
A. For services larger than 400 amperes, prior permission from the Tullahoma Utilities Board must be obtained.
B. The point of service attachment and the meter location shall be approved in advance by an authorized agent of the TUB Electric System.
C. If the service requires a means of disconnect, the service conductors shall be as specified in item I and II, and shall be installed by the contractor or customer from the load side of the meter socket to the line side of the disconnecting means.
VIII. Residential
Primary Line Extensions
A. In general all primary line extensions whether underground or overhead are built at some charge to the customer. A Contribution in-aid-of-Construction charge has been established for the sharing of costs for primary line construction to provide services to that customer.
B. A party requesting extension of a primary line to receive electrical service will pay for the TUB’s non-recoverable costs associated with that extension by making a contribution in-aid-of construction. By definition, the non-recoverable costs shall be considered as all costs except the TUB’s costs for materials.
C. An agreement between the TUB and the requester will be executed prior to the TUB making any part of the installation.
D. The contribution in-aid-of construction must be paid before material will be ordered and/or work will begin.
E. The primary line extension policies apply to all customers or applicants of electric service from the TUB.
F. The customer shall furnish a right-of-way easement for primary line extension and transformer as specified by the TUB representative prior to the TUB making any part of the installation.
G. The customer shall clear the power line right-of-way of trees and obstructions as specified by the TUB representative prior to the TUB performing any part of the installation.
H. The customer shall furnish trenching and conduit on the underground primary line extensions as specified by the TUB representative. The customer is responsible for backfill of trench and repairs of any future trench settling.
NOTE: Providing street lighting is not a part of a primary line extension.
VIIII. Commercial Services
A.
Information needed
for determination of service type:
1. Single phase or three phase.
2. Secondary voltage level required: 120/240, 120/208, 277/480, etc.
3. Current rating of the main switch panel.
4. Diversified KW load.
5. Load breakdown of equipment to be used: motors, air conditioning, heating, lighting, etc.
6. Date requested for final service connection.
7. Any plans for future expansion of business.
8. Overhead or underground service.
9. Business hours of operation per month.
10.Completion of the TUB Power Service Contract.
11.Power line right-of-way easement as specified by the TUB representative.
12.Complete set of stamped drawings with site utility plan, mechanical sections, electrical sections, and electrical panel board schedule.
B.
Customer Requirements:
1. Install service conductor, grounding, conduit, termination cabinets, instrument transformer cabinets, and metering cabinets as per specifications of the TUB, which are calculated from customer information.
2. Provide a readily accessible point on building for termination of the TUB service (overhead or underground).
3. Identify all phase conductors (on three phase installations) with lettering or tape markings throughout the entire installation.
4. Single phase installations shall have black insulation on hot conductors and white insulation on neutral conductor.
5. All insulation from service entrance to main switch shall be THW or THWN unless otherwise noted in the National Electric Code, such as: hazardous locations or high temperature areas.
6. The customer shall install copper conductors from the main breaker or disconnect switch to the instrument transformer cabinet or metering cabinet. In cases where the instrument transformers are located at the pad mounted distribution transformer or pole mount distribution transformers, the customer shall install copper conductors from the main breaker or disconnect switch to transformer(s). The TUB will terminate customer’s service conductors at the transformer(s) or meter cabinet.
7. The customer shall provide a concrete pad for pad mount transformer applications meeting the TUB specifications furnished at later date.
8. The customer shall install meter cabinet on building being serviced by the TUB. Meter sockets or cabinets will not be attached to pad mount transformer or poles.
9. The customer shall furnish and install a 5/8” x 8’ grounding electrode at the meter cabinet and bond cabinet to electrode with continuous run of No. 4 solid bare copper grounding conductor. This additional ground is for metering and cabinet purposes.
C.
Tullahoma Utilities
Board Work Performance:
1. The TUB will install all service cable (overhead or underground) from the point of origin to the instrument transformer cabinet or meter cabinet and make all connections necessary to energize the service when all state electric inspections are made and approved, all applicable fees are paid, and the approval certificate from the City of Tullahoma Codes Department has been issued. In cases where instrument transformers are located at a pad mount distribution transformer or pole mount distribution transformers, the customer shall install copper conductors from the main breaker to the transformer(s) or disconnect switch to the transformer(s). The TUB will terminate the customer’s service conductors at the transformers or meter cabinet.
2. The TUB will furnish the appropriate meter cabinet and/or instrument transformer cabinet for each meter location. Any fabricated cabinets by the customer or contractor must have prior approval of the TUB.
3. The TUB will furnish, locate, install, and maintain the appropriate size transformer(s) for adequate service. The TUB shall have access at all times to the transformer(s) location.
4. The TUB will inform the customer or contractor of any charges for work or materials at each service installation.
D.
Commercial
Underground Service Charges:
1. All underground service charges shall be borne by the customer.
2. Charges include installation of service cable as outlined in item VIIII, C, 1.
3. Upon request, the customer will be provided current underground service charges in accordance with TUB policy E-006 “Underground Service Availability and Charges”, at time service is located by the TUB representative. The customer will be invoiced for underground service charges by the TUB at a later date.
4. All underground service charges must be paid at the TUB office prior to service installation.
E.
Commercial Primary
Line Extensions:
1. In general all primary line extensions whether underground or overhead are built at some charge to the customer. A Contribution in-aid-of-Construction charge has been established for the sharing of costs for primary line construction to provide services to that customer.
2. A party requesting extension of a primary line to receive electrical service will pay for the TUB’s non-recoverable costs associated with that extension by making a contribution in-aid-of construction. By definition, the non-recoverable costs shall be considered as all costs except the TUB’s costs for materials.
3. An agreement between the TUB and the requester will be executed prior to the TUB making any part of the installation.
4. The contribution in-aid-of construction must be paid before material will be ordered and/or work will begin.
5. The primary line extension policies apply to all customers or applicants of electric service from the TUB.
6. The customer shall furnish a right-of-way easement for the primary line extension and transformer as specified by the TUB representative prior to the TUB making any part of the installation.
7. The customer shall clear the power line right-of-way of trees and obstructions as specified by the TUB representative prior to the TUB making any part of the installation.
8. The customer shall furnish trenching and conduit on underground primary line extensions as specified by the TUB representative. The customer is responsible for backfill of trench and future repairs as a result of any trench settling.